תיאור
- Topology: Online (Double Conversion)
Configuration: Tower
Rating (VA/Watts): 2000VA/1800W
Diagnostics: Full system self-test
UPS Bypass: Automatic bypass
Dimensions (H x W x D, mm): 325 x 214 x 410
Weight (kg): 34.5
Remote Emergency Power off (REPO): Emergency shutdown control through the REPO port
Efficiency: 94% in high-efficiency mode; 90% in online mode
- כניסה
- Connection: (1) IEC-320-C14
Input Cord: Schuko 10A to IEC 320-10A
Input Voltage Range: 180-276 Vac (with load PF of 0.7)
Nominal Voltage: 220-240V
Frequency: 50/60 Hz
Frequency Range: 45-65 Hz
Nominal Current: 8.7A @230V
Breaker Ratings: 10A
- יציאה
- Output Receptacles: Aust. 10A
On Utility Voltage Regulation: ±3% of nominal
On Battery Voltage Regulation: ±3% of nominal
Frequency Regulation: ±3% Hz online
Load Crest Factor: 3 to 1
- סוללה
- Battery Description: VRLA 12V/9 Ah (internal and External)
Battery Type: Replaceable maintenance free sealed lead acid
Battery Replacement: Hot-swappable internal batteries
Start On Battery: Allows start of UPS without utility input
- חיבורים
- User Interface: Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish
LEDs: Four status-indicating LEDs
Communication Ports: RS-232 and USB HID port as standard
Relay Output: Common alarm standard
Communications Card Slots: Optional SNMP/Web card for monitoring in SNMP-based networks, monitoring through Web browser interface. Relay card for integration to industrial environment and BMS, remote shutdown for IBM AS/400 systems
- נתוני סביבה
- Heat Dissipation (BTU): Line: 838, Bat: 1348
Audible Noise: <44 dBOperating Temperature: 0C to +40C
Performance – Safety – EMC: CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2), GS
Storage Temperature: -20C to +40C with batteries and -25C to +55C without batteries
Relative Humidity: 5-90% non-condensing
|